Thermocouple vs RTD vs Thermistor

Thermocouples, resistance temperature detectors (RTDs), and thermistors are the three dominant contact temperature sensors. They differ in temperature range, accuracy, linearity, cost, and response. This guide compares them side by side and explains when each is the right choice.

Side-by-Side Comparison

CharacteristicThermocoupleRTD (Pt100)Thermistor
PrincipleSeebeck EMF from dissimilar metalsResistance change of pure platinumResistance change of a semiconductor
Typical range−270 to +2315°C−200 to +850°C−50 to +300°C
AccuracyGood (±0.5 to ±2°C class)Excellent (±0.1 to ±0.5°C)Excellent in a narrow band
LinearityNon-linear (polynomial)Nearly linearHighly non-linear
SensitivityLow (µV/°C)Moderate (~0.385 Ω/°C)Very high
Response timeFast (small junction)Slower (larger element)Fast
ExcitationSelf-poweredRequires current sourceRequires current source
Long-term stabilityModerate; drifts with useExcellentGood to moderate
Relative costLowHigherLow
Governing standardASTM E230 / IEC 60584IEC 60751 / ASTM E1137Manufacturer-specific

RTD figures are for the common platinum Pt100 (100 Ω at 0 °C, temperature coefficient α = 0.00385 Ω/Ω/°C) per IEC 60751. Thermistor ranges vary widely by part; the values shown are typical for general-purpose NTC devices.

Which Sensor for Which Job

Choose a Thermocouple

  • High temperatures above ~600°C
  • Wide range in one sensor
  • Rugged or vibration-prone environments
  • Fast response, small size, low cost
  • Furnaces, kilns, engines, heat treating

Choose an RTD

  • Highest accuracy and stability
  • Moderate range (−200 to +850°C)
  • Repeatable, drift-sensitive processes
  • Lab, pharma, and process control
  • When linearity simplifies the system

Choose a Thermistor

  • Narrow range near ambient
  • Very high sensitivity needed
  • Low-cost consumer and medical devices
  • Point sensing where size matters
  • Not for high-temperature work

Rule of Thumb

If the application exceeds 600 °C or demands ruggedness, use a thermocouple. If it sits within −200 to +850 °C and accuracy and repeatability dominate, use an RTD. If it lives near room temperature and needs high sensitivity at low cost, use a thermistor.